Commercial Boiler Installation in High Wycombe
Heating system upgrade for a community building in Downley, Buckinghamshire
This project involved the replacement of an existing heating system at a community building in Downley, High Wycombe. The installation included two Vaillant ecoTEC Plus boilers, a Megaflo unvented cylinder, a full system powerflush and Honeywell Evohome zoned heating controls.
Planning a commercial heating upgrade?
Call: 01628 533 550
Project Summary
Location: Downley, High Wycombe, Buckinghamshire
Property Type: Commercial community building
Project Type: Planned heating system upgrade
Procurement: Competitive tender
Boilers Installed
- 2 x Vaillant ecoTEC Plus 635
- 2 x Vaillant 1.75m horizontal flue
- 2 x Vaillant 22mm filter boiler protection kit
Cylinder Installed
- Megaflo Eco 210L indirect unvented cylinder
Heating Controls
- Honeywell Evohome Wi-Fi connected thermostat kit
- Honeywell Evohome radiator multi zone kit x3
- Honeywell 15mm angle TRV x12
A Planned Commercial Heating Upgrade in High Wycombe
Community buildings are busy places. Different rooms are in use at different times and the heating system has to keep up with those demands.
When the trustees decided the existing system needed replacing, they put the work out to tender. Several local companies were invited to quote. The Red Van Plumbers won the contract.
Before any work started, our engineers visited the site, assessed the existing system and specified the right equipment for the building’s needs. Getting that groundwork right is what makes the installation straightforward.
The Heating System Installation
Two Vaillant Boilers
For a commercial building of this size, a single boiler is a risk. If it develops a fault or requires servicing, the entire building loses heating and hot water. A twin boiler setup removes that risk. By installing two Vaillant ecoTEC Plus 635 boilers, the system can continue operating on one boiler if the other requires attention. Both boilers work together during periods of high demand and independently when load is lower, which also improves overall efficiency.
Vaillant is one of the UK’s most recognised boiler manufacturers and is widely specified for both domestic and commercial heating systems. The Vaillant ecoTEC Plus range is a reliable and well-proven choice for commercial applications. As Vaillant trained installers, our engineers know the range well and specified the 635 model based on the heating load requirements of the building. You can find out more about our Vaillant boiler installations on our dedicated page.
Loft Plant Room Installation
Both boilers and the unvented cylinder were installed in the loft plant room. Working in a loft space presents its own set of challenges. Access is restricted, working room is limited and all pipework has to be carefully routed to meet current regulations while still allowing reasonable servicing access for the future.
Our engineers planned the full layout before installation began. The photos show a clean, well-organised plant room with neatly run pipework and both boilers and the cylinder positioned for straightforward future maintenance.
Megaflo Eco 210L Unvented Cylinder
A community building with multiple users requires a hot water system that can keep up with demand. The Megaflo Eco 210L indirect unvented cylinder provides high pressure hot water throughout the building, drawing heat from the boiler system to maintain consistent supply.
Unvented cylinders are well suited to commercial buildings because they deliver mains pressure hot water without the need for a cold water storage tank in the loft. This simplifies the system design and improves hot water flow rates across all outlets. Find out more about our cylinder installation and servicing on our website.
System Protection and Powerflush
Before any new equipment was fitted, our engineers carried out a full system powerflush. This process circulates water and specialist cleaning chemicals through the existing pipework and radiators to remove built-up sludge, rust and debris.
Removing contaminants before installation helps protect the new boilers, improve system performance and reduce the risk of future issues. In a commercial environment where reliability is important, this forms a key part of the upgrade process.
An Adey MagnaClean DualXP filter was also fitted to capture any remaining metallic debris and provide ongoing protection for the new heating system.
Find out more about our central heating powerflush service.
Honeywell Evohome Zoned Heating Controls
A community building is rarely heated as a single space. Different rooms are used at different times and by different groups throughout the day and week. A single heating zone covering the whole building wastes energy and fails to meet the varied demands of the space.
The Honeywell Evohome Wi-Fi connected smart thermostat system solves this. It allows each zone to be controlled independently, so only the rooms in use are heated at any given time. Our engineers fitted three multi zone kits and twelve 15mm angle TRV heads across the building, giving precise zone by zone control throughout.
A single channel programmer was also fitted for the nursery and a programmable room stat installed in the hall, ensuring every area of the building has appropriate and independent heating control.
Additional Heating Works
As part of the wider installation, our engineers fitted a new Henrad 700×2000 compact type22 DC radiator in the reception area to improve heating performance in that space. The existing hall radiator was removed, refitted with a new lockshield and thermostatic radiator valve and reinstalled. These additional works ensured that every area of the building benefited from the upgraded heating system, not just the rooms closest to the new plant room.
The Finished Commercial Heating System Installation
The community building now has a modern, efficient heating system designed to meet its specific commercial demands. The twin Vaillant boilers provide reliable heating with built in redundancy. The Megaflo cylinder delivers consistent mains pressure hot water throughout. The Honeywell Evohome system gives the building managers independent zone control across every area of the building.
The full system powerflush and MagnaClean filter protect the new equipment and support the manufacturer warranties on both boilers. The new system has been designed to provide reliable heating, hot water and improved control across the building for years to come.
Commercial Heating Services Across Buckinghamshire and South East England
The Red Van Plumbers carry out commercial plumbing and heating installations for community buildings, care homes, offices, landlords and property managers across Buckinghamshire, Berkshire, South Oxfordshire and West London.
Find out more about our full range of commercial plumbing and heating services, or visit our High Wycombe plumbing and heating page for local service information. You can also view all the areas we cover across South East England.
Planning a Commercial Heating Upgrade in High Wycombe or Nearby?
If your commercial building is due a heating system upgrade, we are happy to visit, assess the existing system and provide a detailed quotation. We work with community buildings, care homes, offices and commercial properties across Buckinghamshire and South East England.
Plumbing and Heating Services Across Bucks
Heppelthwaite – The Red Van Plumbers cover everything your home or business needs. Explore our full range of plumbing and heating services to find out how we can help.